ISOMETER® Iso685-D

The ISOMETER® iso685-D is an insulation monitoring device for IT systems in accordance with IEC 61557-8. It is universally applicable in AC, 3(N)AC, AC/DC and DC systems. AC systems may include extensive DC-supplied loads (such as rectifiers, inverters, variablespeed drives). Insulation monitoring for unearthed systems AC, 3(N)AC 0…690 V, DC 0…1000 V Nominal voltage extendable … Continue reading ISOMETER® Iso685-D

The ISOMETER® iso685-D is an insulation monitoring device for IT systems in accordance with IEC 61557-8. It is universally applicable in AC, 3(N)AC, AC/DC and DC systems.

AC systems may include extensive DC-supplied loads (such as rectifiers, inverters, variablespeed drives).

  • Insulation monitoring for unearthed systems AC, 3(N)AC 0…690 V, DC 0…1000 V
  • Nominal voltage extendable via coupling devices
  • Two separately adjustable response values 1 kΩ…10 MΩ
  • Combination of AMPPLUS and other profile-specific measurement methods
  • Continuous measurement of capacitance, voltage and system frequency
  • Predefined measurement profiles to meet different requirements
  • Automatic adaptation to the system leakage capacitance
  • INFO button to display device and network settings
  • Self-monitoring with automatic alarm message
  • History memory with real-time clock (buffer for three days) for storing 1023 alarm messages with date and time
  • Current and voltage output 0(4)…20 mA, 0…400 μA, 0…10 V, 2…10 V (galvanically separated) which is analogous to the measured insulation value of the system
  • Permanent coupling monitoring of the measuring lines
  • Freely configurable digital and analogue inputs and outputs
  • Two separate alarm relays with potentialfree contact
  • N/O or N/C operation selectable
  • High-resolution graphic LC display
  • IsoGraph function for time-related representation of the insulation resistance
  • Remote setting of certain parameters via Internet (web server/option; COMTRAXX® Gateway)
  • Worldwide remote diagnosis via Internet
  • Modbus TCP, web server and BCOM
  • Multilingual
  • AC, DC or AC/DC main circuits
  • AC/DC main circuits with directly connected DC components, such as rectifiers, converters, variable-speed drives
  • UPS systems, battery systems
  • Heaters with phase control
  • Systems including switched-mode power supplies
  • IT systems with high leakage capacitances
Type Nominal system voltage range Un Supply voltage US Display Option W* Art. No.
iso685-D AC 0…690 V; 1…460 Hz /
DC 0…1000 V
AC 100…240 V; 47…460 Hz /
DC 24 V, 100…240 V
X B91067010
iso685W-D* AC 0…690 V; 1…460 Hz /
DC 0…1000 V
AC 100…240 V; 47…460 Hz /
DC 24 V, 100…240 V
X -40…+70°C,
3K5, 3M7
B91067010W
iso685-S + FP200 AC 0…690 V; 1…460 Hz /
DC 0…1000 V
AC 100…240 V; 47…460 Hz /
DC 24 V, 100…240 V
B91067210
iso685W-S + FP200* AC 0…690 V; 1…460 Hz /
DC 0…1000 V
AC 100…240 V; 47…460 Hz /
DC 24 V, 100…240 V
-40…+70°C,
3K5, 3M7
B91067210W

Other products

POWER MANAGEMENT WITH PEM735

POWER MANAGEMENT WITH PEM735

The digital universal measuring device PEM735 is designed for measuring and displaying electrical quantities of electricity networks