ISOMETER® Iso685-D
The ISOMETER® iso685-D is an insulation monitoring device for IT systems in accordance with IEC 61557-8. It is universally applicable in AC, 3(N)AC, AC/DC and DC systems. AC systems may include extensive DC-supplied loads (such as rectifiers, inverters, variablespeed drives). Insulation monitoring for unearthed systems AC, 3(N)AC 0…690 V, DC 0…1000 V Nominal voltage extendable … Continue reading ISOMETER® Iso685-D
The ISOMETER® iso685-D is an insulation monitoring device for IT systems in accordance with IEC 61557-8. It is universally applicable in AC, 3(N)AC, AC/DC and DC systems.
AC systems may include extensive DC-supplied loads (such as rectifiers, inverters, variablespeed drives).
- Insulation monitoring for unearthed systems AC, 3(N)AC 0…690 V, DC 0…1000 V
- Nominal voltage extendable via coupling devices
- Two separately adjustable response values 1 kΩ…10 MΩ
- Combination of AMPPLUS and other profile-specific measurement methods
- Continuous measurement of capacitance, voltage and system frequency
- Predefined measurement profiles to meet different requirements
- Automatic adaptation to the system leakage capacitance
- INFO button to display device and network settings
- Self-monitoring with automatic alarm message
- History memory with real-time clock (buffer for three days) for storing 1023 alarm messages with date and time
- Current and voltage output 0(4)…20 mA, 0…400 μA, 0…10 V, 2…10 V (galvanically separated) which is analogous to the measured insulation value of the system
- Permanent coupling monitoring of the measuring lines
- Freely configurable digital and analogue inputs and outputs
- Two separate alarm relays with potentialfree contact
- N/O or N/C operation selectable
- High-resolution graphic LC display
- IsoGraph function for time-related representation of the insulation resistance
- Remote setting of certain parameters via Internet (web server/option; COMTRAXX® Gateway)
- Worldwide remote diagnosis via Internet
- Modbus TCP, web server and BCOM
- Multilingual
- AC, DC or AC/DC main circuits
- AC/DC main circuits with directly connected DC components, such as rectifiers, converters, variable-speed drives
- UPS systems, battery systems
- Heaters with phase control
- Systems including switched-mode power supplies
- IT systems with high leakage capacitances
Type | Nominal system voltage range Un | Supply voltage US | Display | Option W* | Art. No. |
---|---|---|---|---|---|
iso685-D | AC 0…690 V; 1…460 Hz / DC 0…1000 V |
AC 100…240 V; 47…460 Hz / DC 24 V, 100…240 V |
X | – | B91067010 |
iso685W-D* | AC 0…690 V; 1…460 Hz / DC 0…1000 V |
AC 100…240 V; 47…460 Hz / DC 24 V, 100…240 V |
X | -40…+70°C, 3K5, 3M7 |
B91067010W |
iso685-S + FP200 | AC 0…690 V; 1…460 Hz / DC 0…1000 V |
AC 100…240 V; 47…460 Hz / DC 24 V, 100…240 V |
– | – | B91067210 |
iso685W-S + FP200* | AC 0…690 V; 1…460 Hz / DC 0…1000 V |
AC 100…240 V; 47…460 Hz / DC 24 V, 100…240 V |
– | -40…+70°C, 3K5, 3M7 |
B91067210W |
Quick start FP200
http://www.bender-de.com/fileadmin/products/q/FP200_D00169_Q_INTE.pdf
Datasheet FP200
http://www.bender-de.com/fileadmin/products/doc/FP200_D00169_D_XXEN.pdf
Brochure iso685
http://www.bender-de.com/fileadmin/products/b/e/iso685_PROSP_en.pdf
Datasheet iso685-D
http://www.bender-de.com/fileadmin/products/doc/iso685-D_D00022_D_XXEN.pdf
Operating Manual iso685-D
http://www.bender-de.com/fileadmin/products/m/e/iso685-D_D00022_M_XXEN.pdf
Operating Manual iso685-… Annex A
http://www.bender-de.com/fileadmin/products/m/e/iso685_D00022_A_XXEN.pdf